• Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!

  • Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.

Search results

  1. D

    804A power transfer issue

    Guy, No voltage at X,Y at K1, with Main SW in run position, battle short on, S5 Up, To ensure the contactor was in good shape, I removed it. Was a bit sticky, No sign of any water or rust, contacts needed dressing up. Coil measured 43 ohm. Ran out of daylight, will test coil / contactor with 24...
  2. D

    804A power transfer issue

    Good morning Guy, All the more reason to get this genset under cover. Weather here this morning looks a bit ominous, but the investigation exercise shouldn’t take all that long. I’ll report back.
  3. D

    804A power transfer issue

    Guy, Understood, in locating K1 (power transfer contactor, it is a bit Inaccessible, it appears the top of the genset will need to be removed for adequate accessibility.)Rain is forecasted here in the New Hampshire, this machine is not yet undercover. I’ll respond once troubleshooting procedure...
  4. D

    804A power transfer issue

    Guyfang Sir, Thank you. I’ll report back when procedure’s completed.
  5. D

    804A power transfer issue

    Evvy, Understood appreciate it, thank you for the clarification. Communication thus far is clear.
  6. D

    804A power transfer issue

    Guyfang Sir, S1 in Run position , (unit not started S1 only in run position), S7 battle short SW up lamp is illuminated. S5 AC interrupter SW up, lamp is not lit, no clunk heard, (as it seems contactor does not pull in, assuming that’s the clunk you are referring to?)
  7. D

    804A power transfer issue

  8. D

    804A power transfer issue

    Guyfang Sir, S5 contactor switch up, on, S7 AC contactor light not on.
  9. D

    804A power transfer issue

  10. D

    804A power transfer issue

    Kloppk, Yes Sir reasonably well with a meter. No fault lamps when restarted.
  11. D

    804A power transfer issue

    Mullaney, Thank you I’ll take a look, if it gets too deep may be beyond my skill set. Any idea in my area that a qualified service person or company. So west NH.
  12. D

    804A power transfer issue

    Genset has 100 hrs on it. Was operating fine, making power. I shut down to adjust fan belt, and change oil. Now seems doesn’t transfer power, power is generated to line side of contactor, transfer panel mounted transfer switch seems fine. Any ideas ? Any problematic known issues?
  13. D

    Mep804A engine element heater

    The northeast cold weather challenges the Issuzu 4 cylinder diesel starting. I’m looking to add a coolant element heater, it appears there is one 3/4” threaded port (likely metric) fan facing front right side of engine, toward the back of the block ? And if not then a freeze plug port for a...
  14. D

    MEP804A Hertz Gauge

    Please note the eBay listing did state MEP802, 803, 804, 805, 806 So yes I think the part number 60.1034 will fit other models than my 804A
  15. D

    MEP804A Hertz Gauge

    Appreciate your response Thank you, another member also responded, and located the gauge. Ebay 60$ new. my issues solved. My gauge was in working condition just was a bit sticky My gauge was a 48-62 Hertz and "Ideal" manufacture, part number 60.1034. Thanks again
  16. D

    MEP804A Hertz Gauge

    Thank you very much, Ebay hit on OEM 60.1034 Exactly what I needed and new. Thanks again.
  17. D

    MEP804A Hertz Gauge

    Looking for a OEM Hertz Gauge for a MEP804A Genset any sources out there? Part #88-21072 (from the tech manual)
Top
AdBlock Detected

We get it, advertisements are annoying!

Sure, ad-blocking software does a great job at blocking ads, but it also blocks useful features of our website like our supporting vendors. Their ads help keep Steel Soldiers going. Please consider disabling your ad blockers for the site. Thanks!

I've Disabled AdBlock
No Thanks