  1. R

    Mep-002A 003A 004A 005A Drop in Spin on Fuel filter adapter

    I'll send you over a private message. Looks like you are too new to be able to send a PM yourself.
  2. R

    What did I find in the bottom of my MEP?

    Looks unrelated to your 802. I don't think I've ever seen anything like that anywhere in an 802 , unless it came from inside the fuel pump or something, that's one place I've never been... I usually pluck em' and chuck em' when they die, never opened one, not that I think you even can open a...
  3. R

    803A droop adjust screw?

    The oil light should stay off above 18 PSI, but the gage is not the determining factor and could be inaccurate. There is a pressure sensor near the gage sending unit that triggers the low oil pressure shut down. RPM should be 1800 ( 60Hz on the gage ) RPM is directly responsible for AC...
  4. R

    803A droop adjust screw?

    Did you notice any fault lights on while the solenoid was trying to shut it down? If there is a fault found, the relay will kill power to the solenoid to shut the machine down. The issue with the throttle knob not having any effect still points towards a governor / fuel rack / metering pump...
  5. R

    MEP-802A questions

    There is no need for a vapor barrier on an outdoor slab. In fact, some say it can cause problems outdoors by trapping moisture from rain, that makes its way through the concrete, in between the plastic and the bottom of the slab. This can supposedly deteriorate the concrete or freeze in cold...
  6. R

    MEP-802A questions

    Shouldn't have the remesh wire touching the form, it should be fully encapsulated in the concrete, 2" min away from the form, but.. this is a generator pad, not the Washington Bridge.... :ROFLMAO: ( not sure how many of you are aware of the problem with the bridge on 195 in RI ) so it will be...
  7. R

    803A droop adjust screw?

    I think you may have 1 pump adjusted differently than the others, causing the rack to stop short of the screw and holding the other pumps slightly open. On the rack motion, I don't think it's possible for the rack to really hang up or move slowly ( due to a sticky pump lever etc.) IF the outside...
  8. R

    803A droop adjust screw?

    Once you have all 4 pumps oriented correctly test it again. If you still have the same problem, loosen the jam nuts on the stop screw that the the shut off lever hits when the solenoid pushes it forward. (If the screws are in the original setting they typically have red indicating compound on...
  9. R

    MEP-802A questions

    Almost... I believe Mainsail bolted the lower blocks to the pad then lagged the upper block through the frame and into the lower blocks. This will work fine, but gives you a bunch of unnecessary added height. I would put your bolts into the concrete with the thread up. Use bolts with washers...
  10. R

    MEP-802A questions

  11. R

    803A droop adjust screw?

    That's helpful information! Previous posts kind of sounded like the solenoid action was delayed after turning off S1 but was the solenoid reacted immediately when hitting the E-stop. You may have the metering pumps adjusted incorrectly. Are all 4 sitting in the block with the fuel supply hoses...
  12. R

    803A droop adjust screw?

    The solenoid has 3 wires. A black common and 2 colored inputs, 1 from the cranking relay and the other from the malfunction indicator. Take a look at the schematic and you can follow the wires. Also below is a picture of the connector wiring at the FSS. Pin 1 at the FSS should have power when...
  13. R

    803A droop adjust screw?

    Because something is wrong with the 10K ;) Seriously, both should act identically. There should not be any delay and there should be no difference between an 802 and an 803. Something electrically is wrong with your 803 if power doesn't disconnect and the solenoid extend out immediately when...
  14. R

    803A droop adjust screw?

    Either way, E- stop or S1, killing power to the fuel solenoid, causing its plunger to spring forward, pushing the rack forward rotating the metering pump pins to the fuel-off position is the ONLY way to shut it off. With it running, watch what the solenoid does when you turn S1 off. it should...
  15. R

    Mep-003 donor engine

    Good work getting it going again! In the video I could briefly see the volt gage, which looked to be way above 240V ( assuming you have the machine set to 120/240). Before you go too much further, verify the output voltage. If it can't be adjusted down with the knob, you may have blown...
  16. R

    Generator Libby MEP-003A

    If you are needing to update filters, I would strongly suggest swapping out the stock canisters and going with @Ray70's fuel upgrades for the 00X machines. Well worth it for long term owners, and better filtering and EASIER changes! I tagged him, because I'm not sure if they are up in the...
  17. R

    Generator Libby MEP-003A

    If you can get a video together that would be great. Thinking more about your problem, I'm wondering if you have an issue with your rocker arm adjustments? It's starting to sound like you may be loosing compression as the motor heats up, possibly from the rocker arms being set too tight and...
  18. R

    MEP-802A Water pump/fan retainer nut?

    When you get to tightening your fan nut, make sure its facing the right way. It should be flat on 1 side ( outside ) and have a round "collar" looking protrusion on the other. That round protrusion with the recessed center goes against the pump to allow the nut to put pressure on the fan blade...
  19. R

    Generator Libby MEP-003A

    slowly beginning to mis and then slowly die after a few minutes sounds like a fuel supply problem. Do as the others have suggested by cleaning the fuel system. In addition to cleaning the bottoms of the pumps and screens, listen to the pumps while they are powered on. They should both click...
  20. R

    MEP 804a

    Judging by the markings on the wires at K1, someone else has messed around in there before!