  1. R

    MEP804A will crank second then over speed fault occurs

    confirmed. Control cube look different than the rest and has button ( try’s to post pic but having problem )
  2. R

    MEP804A will crank second then over speed fault occurs

    I removed, inspected and used a vault meter to test the relay and its plug ....... I think I fallowed some instructions I found on another post. Any tips or tricks on testing the relays would be much appreciated
  3. R

    MEP804A will crank second then over speed fault occurs

    I’m back ... removed, inspected MPU ( no damage) Reinstalled MPU and adjusted to now 2.3vac direct Turn s1, set will crank for split second and stop. overspeed fault indicator illuminated . I found the power potential transformer but haven’t tested yet ... I bet that’s the under voltage...
  4. R

    MEP804A will crank second then over speed fault occurs

    Will inspect MPU and readjust to 2.3vac direct will update when completed As for the power potential transformer I shall begin my investigation
  5. R

    MEP804A will crank second then over speed fault occurs

    👍🏻👍🏻... thanks I’ll remember that
  6. R

    MEP804A will crank second then over speed fault occurs

    Update something different is happening now after unplugging the fault indicator When I try start the set with battle short on it no longer cranks but under voltage and low oil shutdown fault lights go on ................umm maybe I’ve lost my marbles on this one but I thought the battle short...
  7. R

    MEP804A will crank second then over speed fault occurs

    I discontented plug on fault indicators ( box with fault light ) I turn s1, set cranks for split second then stops Reconnected plug Tried to start set again same thing overspeed lights up set cranks for one second stops Tried to start with battleshort switch on, set will crank for a...
  8. R

    MEP804A will crank second then over speed fault occurs

    I turn s1 and hold 10 sec, generator will crank for split second then the engine stop overspeed light goes on, generator stops and will not crank .... also fallowed flap instructions and TM 9-6115-643-10 troubleshooting section
  9. R

    MEP804A will crank second then over speed fault occurs

    I am trying to get a Mep804a running with 108 hours, when I first got the generator it would crank but not start, I discovered the MPU missing and replaced it (nsn 6695-01-367-9723,88-21061) and adjusted to 2.88acv at A5 ( woodward gov control ) Now generator will crank for a second then The...