• Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!

  • Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.

Search results

  1. 9

    802A engine fuel pump

    Does anyone have the NSN for the engine fuel pump on a 802A with an Onan engine. I found a part # 486-6151, but no cross reference to an NSN anywhere. Any help will be appreciated.
  2. 9

    802 relay assist

    Will do that, thank you. I searched for M3 and took me to this thread. Thats why I followed.
  3. 9

    802 relay assist

    Hello everyone, following this thread, the M3 (time meter) is contantly ticking, even when the DC fuse is out. Anyone experienced this problem on a 802A?
  4. 9

    Gen set 804A 15k No volt, no freq

    Awesome! fixed the problem right away, thank you everyone.
  5. 9

    Gen set 804A 15k No volt, no freq

    Thank you.
  6. 9

    Gen set 804A 15k No volt, no freq

    Thank you for the reply. I will try to find a fuse, it came to our shop without it. Will update when I get it.
  7. 9

    Gen set 804A 15k No volt, no freq

    Following this thread. My problem is that while holding on start position ,the voltage and frequency is good, as soon as I release the S1, the under voltage light illuminates and lose power. Here is the picture of the voltage regulator currently installed on this generator (MFD 11/93), I circled...
  8. 9

    804A, Percent Rated Current, Percent Power Gauges

    We figured out, one of the ordered Gauges came defective, works when the control panel door is open and facing down, the other one, one of the wires in the bundle that moves when opening the panel door was cut due to friction. Thank you for taking the time and try to help. Appreciate it.
  9. 9

    804A, Percent Rated Current, Percent Power Gauges

    With Generator running, with load (using Freedom Loadbank) I get 120V on each one of those to N.
  10. 9

    804A, Percent Rated Current, Percent Power Gauges

    Yes, output is good, Load Bank reads voltage as it should, everything works, except the two gauges.
  11. 9

    804A, Percent Rated Current, Percent Power Gauges

    Performed tests from Paragraph 2-29.2 Ammeter Gauge, the result: Replace Gauge, Test 2-30.2 gave no Voltage in wires. Using Wiring Diagram took me to the Kilowatmeter Transducer, Test 2-53.2, which resulted in measurement out of range. The rotary switch, we had a new one, since the wires to the...
  12. 9

    804A, Percent Rated Current, Percent Power Gauges

    I'm currently working on a 804A Generator, replaced the Percent Rated Current and Percent Power Gauge, new Rotary Switch and Watt Transducer, Gauges are still Inop. Anyone had the same issue? if so, what was the fix? Thanks in advance.
Top
AdBlock Detected

We get it, advertisements are annoying!

Sure, ad-blocking software does a great job at blocking ads, but it also blocks useful features of our website like our supporting vendors. Their ads help keep Steel Soldiers going. Please consider disabling your ad blockers for the site. Thanks!

I've Disabled AdBlock
No Thanks