    MEP-804B no output

    Yes I did reset the GFCI still now power coming out of it.
  2. P

    MEP-804B no output

    There is power coming into but not out of the breaker for the outlet. PN:19990-2. I have been looking for one but they seem hard to find. Might for the time being remove it and install an 10amp inline fuse or similar breaker. Is there some other component or control box the outlet runs through...
  3. P

    MEP-804B no output

    Yes, they are awesome. It seems to be operating now. I appreciate all the help. I will have to build an output cable to load test now that it appears to be working. The only other issue that I am working on now is the courtesy outlet is not working. It is putting out 4.5 volt AC. The breaker is...
  4. P

    MEP-804B no output

    Ok I will get on that next and report back. Need to go find a micro flat head. From what I can tell it seems to be kicking off over speed currently around 61-62
  5. P

    MEP-804B no output

    Have reset the overspeed switch several times. After starting and running the unit quite a bit, it appears to be operating and putting out power but still having a frequency issue or sensitivity. Sometimes on start up it will shut down for overspeed immediately and sometimes it will run. If you...
  6. P

    MEP-804B no output

    Got the contactor to close and do have voltage at all of the lugs. Still having an issue with the generator shutting down for overspeed warning. With both the freq and volt turned all the way down on the 50 hz switch side running reading 53 once you close the contactor and get a light 58 with...
  7. P

    MEP-804B no output

    Replaced the fuse and video attached. The frequency and voltage are now coming up and both adjustable with potentiometer knobs, it seems to easily flag "overspeed" and shut off with red indicator. I still am getting 0 voltage to the output cable box lugs and only 4.5 volts on the courtesy...
  8. P

    MEP-804B no output

    Thank you for all of the helpful information. I opened up the top of the control box and it is TRC regulator listed PN: 30554 and 19870. I am currently looking for the testing procedure and will let you know what I find. There is also tube fuse on the rear wall on the left side of the regulator...
  9. P

    MEP-804B no output

    I have an MEP-804B that was suppose to work but has no output. The engine cranks and runs really well but no voltage on any of the 3 lugs. Both freq and volt potentiometers have no real affect on the meter, however you can hear a rpm pick up while turning the freq. Also the convenience...