This is an extract from TM 9-6115-661-13&P. There are several types of generator set ups, that use a synchronizing circuit, (so called "switch box" below) to allow you to parallel and switch the load from one generator set to another. The rig is simple, and not hard to find. It would allow you to hook up the gen set and street power, parallel both, and change power sources. Your real problem is that the gen set is three phase. Your street power is not. Its still doable, if you find someone smart.
There is no difference between a MEP-805A and MEP-805B, other then the engine.
Power Plant AN/MJQ-39 and AN/MJQ-39A. The AN/MJQ-39 and AN/MJQ-39A Power Plant consists of two
PU-800 Power Units, a power cable and a switch box. The PU-800 Power Units have been identified as either
Unit A or Unit B. The Switch Box is mounted on Unit A and the power cable is stored on Unit B. The electrical
output and towing information are the same as listed for the PU-800 in the Capabilities and Features section in
Table 5 below.
Power Plant AN/MJQ-48. The AN/MJQ-48 Power Plant consists of two PU-801 Power Units, a power cable and
a switch box. The PU-801 Power Units have been identified as either Unit A or Unit B. The Switch Box is mounted
on Unit A and the power cable is stored on Unit B. The electrical output and towing information are the same as
listed for the PU-801 in the Capabilities and Features section in Table 11 below.
Power Plant AN/MJQ-48A and AN/MJQ-48B. The AN/MJQ-48A and AN/MJQ-48B Power Plants consists of two
PU-801A Power Units, a power cable and a switch box. The PU-801A Power Units have been identified as either
Unit A or Unit B. The Switch Box is mounted on Unit A and the power cable is stored on Unit B. The electrical
output and towing information are the same as listed for the PU-801A in the Capabilities and Features section in
Table 11 below.
1. I will correct myself. Yes there is a difference between the 805A and 805B. The 805A has a "normal" control panel. Not touch screen, and there are components in the control panel different. I was thinking of the MEP-804A and 804B models.
2. It would be very difficult to change a 805A to a 805B model. Just a quick look in the parts manuals will, or should convince you of that. They are two different animals. They do not even share the same engine. Not even Macgyver could have much chance of accomplishing that feat.
3. Chris is 1000% correct. You can not convert that gen set.
4. Analog or digital, has nothing to do with your problem. To accomplish what you want to do, you need a way to synchronize your phases. Switching between two different power sources,
without interruptions, is NOT possible without synchronizing/paralleling the power sources. I have seen what happens when that doesn't go right. Its not pretty. Now if what you want to do is switch power sources, WITHOUT all this fuss, you simply need a switch that cuts off one power source, and turns on the other. But you WILL have an interruption. Every system plugged into your fire station will lose power, and shut down. Some systems wont make a big deal. Other things sure don't like that. Computers for instance.
5. The for mentioned "Switch Box" allows you to monitor that fact that you have two power sources. It allows you to parallel the power sources. It allows you to move your load, (fire station) from one, to the other power source, without interruption.