Does anyone have good experiences with the MEP-803s and UPS loads? I have 4 of them. I'm hoping someone will tell me they're going to beep periodically and don't worry about it.
A couple of times during testing the MEP with my house loads, my standby APC UPS (consumer grade) will beep indicating the AC power isn't "clean". I don't have any way to tell if that's voltage drop, voltage spike, or frequency change out of spec.
I am pretty sure it happened when my heat pump compressor was starting. I have a soft start kit and am certain I had plenty of capacity. The load before it started was 2kW. Before any of this happened, my CT monitoring system in my garage said my voltage was above 240V and frequency above 60Hz.
I haven't been able to reproduce the problem while watching my CT system or clamp on meters. I am honestly a bit nervous testing with my house as a test load and my DIY load bank testing never showed any problems above 100%.
Does anyone know of a way I can monitor my voltage and frequency remotely or something that will log it?
A couple of times during testing the MEP with my house loads, my standby APC UPS (consumer grade) will beep indicating the AC power isn't "clean". I don't have any way to tell if that's voltage drop, voltage spike, or frequency change out of spec.
I am pretty sure it happened when my heat pump compressor was starting. I have a soft start kit and am certain I had plenty of capacity. The load before it started was 2kW. Before any of this happened, my CT monitoring system in my garage said my voltage was above 240V and frequency above 60Hz.
I haven't been able to reproduce the problem while watching my CT system or clamp on meters. I am honestly a bit nervous testing with my house as a test load and my DIY load bank testing never showed any problems above 100%.
Does anyone know of a way I can monitor my voltage and frequency remotely or something that will log it?