I am trying to get a Mep804a running with 108 hours, when I first got the generator it would crank but not start, I discovered the MPU missing and replaced it (nsn 6695-01-367-9723,88-21061) and adjusted to 2.88acv at A5 ( woodward gov control )
Now generator will crank for a second then The overspeed fault light goes on and generator stops.
When I turn S7( battle short ) On the gen set would crank for a sec then the under voltage fault light goes on and gen set stops
I’ve checked all relays they seem to be working with good connections
I tried using overspeed reset, didn’t seem to do anything
Gonna dive back in to the -10 TM and -24 TM trouble shooting Section and make sure I didn’t miss anything
Any help much appreciated
Now generator will crank for a second then The overspeed fault light goes on and generator stops.
When I turn S7( battle short ) On the gen set would crank for a sec then the under voltage fault light goes on and gen set stops
I’ve checked all relays they seem to be working with good connections
I tried using overspeed reset, didn’t seem to do anything
Gonna dive back in to the -10 TM and -24 TM trouble shooting Section and make sure I didn’t miss anything
Any help much appreciated