Hello, I have a MEP-806A Generator that will start and run, but not produce any voltage when holding switch to start or releasing. I have a contactor trip under voltage light illuminated. I did the 4.1 voltage regulator test, from the TM, and determined that the transformer may be the issue, as terminals 11 and 12 do not produce power. I checked for continuity through the droop current transformer, and it was ok. I did find the 2 wires going from the main transformer to TB1 were both shorted out and burnt through in a few places. I replaced those 2 wires and still having the same issues. Could this be a bad main transformer? Or how would i go about sourcing a correct Libby transformer replacement? Any advice or feedback is welcome! thank you