Rik
Member
- 36
- 24
- 8
- Location
- California
I have a MEP-804B (Yanmar Engine) and I have a problem that just developed.
I was using the Generator and shut it off for a few minutes and then when I went to restart I get nothing, meaning the fuel pump does not run, the engine will not turn over and thus will not start.
History: Unit has 470 hrs on it and performs excellent. In the past when I turn the ignition switch to start it cranks over and starts or I hear a click, if I hear a click I simply turn the switch to off and repeat and for some reason the 3rd attempt (if it does this) is starts and on with life.
Trouble shooting:
I checked the batteries and they are putting out 25V
I can jump the starter and the motor spins over but does not fire up
I checked the breaker behind the panel (7.5 amp) and it has 25V in and out
I checked the power to the ignition switch and it has 25V on terminal #8
I checked the voltage at the starter and it has 25V
I went to the dead crank switch and it is in the run position but it will not crank over the motor when I flipped the switch to the crank position
I made sure that the emergency shut off was in the run position
So:
I thought it was the ignition switch so I purchased on from 'Green Mountain" and I just changed it and to my surprise the problem still exist.
What could cause the engine to not start, crank, turn on the fuel pump, open the fuel cutoff ??? Is there a breaker somewhere that I do not know of?
Thanks in advance.
I was using the Generator and shut it off for a few minutes and then when I went to restart I get nothing, meaning the fuel pump does not run, the engine will not turn over and thus will not start.
History: Unit has 470 hrs on it and performs excellent. In the past when I turn the ignition switch to start it cranks over and starts or I hear a click, if I hear a click I simply turn the switch to off and repeat and for some reason the 3rd attempt (if it does this) is starts and on with life.
Trouble shooting:
I checked the batteries and they are putting out 25V
I can jump the starter and the motor spins over but does not fire up
I checked the breaker behind the panel (7.5 amp) and it has 25V in and out
I checked the power to the ignition switch and it has 25V on terminal #8
I checked the voltage at the starter and it has 25V
I went to the dead crank switch and it is in the run position but it will not crank over the motor when I flipped the switch to the crank position
I made sure that the emergency shut off was in the run position
So:
I thought it was the ignition switch so I purchased on from 'Green Mountain" and I just changed it and to my surprise the problem still exist.
What could cause the engine to not start, crank, turn on the fuel pump, open the fuel cutoff ??? Is there a breaker somewhere that I do not know of?
Thanks in advance.
Last edited: