So I have an 803A that I used during hurricane helene. She worked great except I noticed that the frequency drops from 60hz to 56hz when my water heater is on. Load meter only shows a 25% load during this condition, so I doubt it's a load issue. I think this is a governor issue because I found if I turn the frequency adjusting knob to up 64hz unloaded, then the generator drops to 60hz under the load of the water heater. This tells me that it isn't a fuel issue or some sort of lack of power problem. The generator has the power to run my water heater at 60hz, but it drops by 4hz under load. Is there a way to adjust this?
I seem to recall something about a droop screw for adjusting frequency droop but I can't seem to find any reference to this. Wondering if you guys might have the answer.