  1. C

    MEP-002A quit generating under full load. Where to start

    And much thanks TripleJim and all others!
  2. C

    MEP-002A quit generating under full load. Where to start

    Ok. I'm will hopefully get the other board tomorrow. It looks just a bit different. The rheostats are a different form factor (long and rectangle vs mine that are small and square). I can't help but wonder if I should be testing the transformer and anything else in the circuit. I don't see...
  3. C

    MEP-002A quit generating under full load. Where to start

    Cuad4u- I checked the voltage adjust rheostat and it was indeed 0-1k ohms
  4. C

    MEP-002A quit generating under full load. Where to start

    TripleJim for the win!!!! Disconnected wire 17 at the voltage regulator and I have 165 VAC! I'll swap it out and keep everyone posted. I should be able to repair the old one, but it may test my skills...
  5. C

    MEP-002A quit generating under full load. Where to start

    Voltage adjustment rheostat seems fine.
  6. C

    MEP-002A quit generating under full load. Where to start

    I was reading an old thread over on ,smokestack and it was saying the exciter field should be getting 12vdc when holding start switch to start with unit running. I'm only getting 5, but it is generating while it is flashing. I guess this is a clue. It is possible my voltage adjustment...
  7. C

    MEP-002A quit generating under full load. Where to start

    Thanks Triple Jim. I'll give it a shot. Luckily I have a couple parts gensets nearby where I bought mine. I just hope it isn't the actual generator head.
  8. C

    MEP-002A quit generating under full load. Where to start

    The regulator board looks ok. I see the bench test procedure in the manual, but it looks like quite a process. I think I have to pull it and two transformers and wire in two switches. I was hoping for an easier way to test it. I know overload can cause field collapse. Is there some...
  9. C

    MEP-002A quit generating under full load. Where to start

    I was talking about the diode bridge board, but I pulled it and checked all 6 diodes and the resistor. That was all fine.
  10. C

    MEP-002A quit generating under full load. Where to start

    I see that diode CR6 is a bit discolored/malformed. CR1, 2 and 3 seem to test ok, but CR 4, 5, and 6 all go to the same terminal on the board, and not sure what I should be reading if they are working properly without removing that board. It seems like the whole board is potted, so I can't...
  11. C

    MEP-002A quit generating under full load. Where to start

    Thanks for the reply. I did try that, but it wasn't tripped. There is also no voltage at the auxiliary outlet. I was just messing with it and found that if I hold the starter switch to start when the set is running, it outputs voltage to the outlet. I was doing this to reflash the magnetic...
  12. C

    MEP-002A quit generating under full load. Where to start

    My genset quit on me in the middle of a power outage a couple nights ago. The motor struggled for a second, it stopped generating, then the motor recovered to full RPM with no output voltage. It starts right up now, but only outputs 1 vac. Any help with how to troubleshoot would be very...