I put that flight systems model 480 Universal regulator on this genset capable of 90 volts DC at 5 amp. I have the the field positive output of the regulator going through that 3 amp fuse so that it's still protected at the factory rating
The way I have it wired now the primary Supply wires to the Transformer are inputs to the new regulator I have the new regulator has an output to the F1 and F2 positive and negative. Four wires total I'm wondering if it will work like that because the old regulator is out and all those wires...
No I did not hardwire the generator I did put another 3 amp fuse in it . The fuse that I used was not a fast blow type fuse one vendor said it would be okay so I tried it didn't work. So I sent the regulator off and had it repaired got it back and it ran for about 5 minutes producing power and...
replaced voltage regulator kept blowing 3amp fu2 fuse . installed flight sys regulator aftermarket . dont know if regulator will work with this unit . i check power at f and j on diagnostic connector over 9 volts to f1 and f2 circiut while start switch is in crank position. 200 volts 60 hz...
i have mep 804 b will not produce elec i replace voltage regulator with a new one from flight systems old one would blow 3amp fuse still no power after i let off start switch.
i sent voltage reg to flight systems for our 804 b yanmar yesterday brian clogner it blows 3amp fuse f1 circuit i ohmed the circiut to gen 33 ohms. does any one know wix filter numbers for 804a isuzu oil and both fuel and air