Search results

  1. K

    MEP-1040 Owners

    I believe that's the ground cable that gets attached to the ground rod. It's suppose to be about 5' long according to the -10 TM. From the picture it appears to be folded up. When used the braid is fed out one of the holes in the side of the set and it gets attached to the ground rod.
  2. K

    Anyone have a Mep 802A fU1 FUSE or konow of an equivalent fuse (F03A125V30A) ?

    It could be that diode CR1 failed. If it fails you loose all 24 volt power and you cannot dead crank the set. CR1 is a 1N5405 3 amp diode. In a pinch you can put a jumper across the terminals that CR1 is soldered to to restore power.
  3. K

    MEP-804B

    Sry, nothing for the 805B or 806B
  4. K

    Anyone have a Mep 802A fU1 FUSE or konow of an equivalent fuse (F03A125V30A) ?

    For fuses the voltage rating needs to be equal or higher than the voltage being protected. A higher voltage rated fuse will work just as well as one rated closer to the voltage being protected. Generally a fuse rated for 120 VAC came be used to protect a DC circuit up to 60 volts. One half the...
  5. K

    Anybody parting out an 804a?

    Mounting bracked is PN 5197110850 5340-01-414-2903 It in TM 9-2815-254-24P
  6. K

    mep 803a power at lugs one time

    When running with S5 in the center position S5-5sshould have 24 volts on it. When you lift S5 S5-5 should go to 0 volts. Seems that's what you have working now. With the set running and you lift and HOLD S5 UP does the Contactor lamp illuminate? Does it stay illuminated when you release it?
  7. K

    mep 803a power at lugs one time

    Do you mean no continuity between TB5-16 and J6-35?
  8. K

    mep 803a power at lugs one time

    I you had 24 volts at K1-Y and nothing at TB5-16 then it could be a problem with the connection between P6 & J6. With the set OFF and Dead Crank in OFF unplug P6 from J6. Access from the right door under the gauge panel. You'll need to turn the locking collar on P6 CCW to unlock it before you...
  9. K

    mep 803a power at lugs one time

    Leave it plugged in and check all the other points along the path. If what you get for measurements points to a P6/J6 problem then we'll need to do some resistance checks with the set OFF.
  10. K

    mep 803a power at lugs one time

    TB5 is the long terminal strip behind the row of relays J6 Visible in this pic. P6 is plugged into it from underneath the compartment.
  11. K

    mep 803a power at lugs one time

    If no 24 volts at S5-5 with the set running then there is a problem with the 24 volts getting from K20 the Oil Pressure relay all the way to S5-5. Here is the path from K20-6 all the way to S5-5. With the set running start at K20-6 verify 24 volts DC is there and continue down the path until...
  12. K

    Converting a MEP-831A to standard generator

    A friend of mine ended up with an extra new Alt Mecc generator generator head for doing the 831 conversion. He has no need for it and is looking to sell it. If interested contact Mark at: mark.neil@verizon.net He's located in S.E. Massachusetts update: sold
  13. K

    mep 803a power at lugs one time

    I assume when you say "nothing" it means the contactor lamp did NOT illuminate. So.... 1) When you had the set running where there any Fault lamps illuminated. If unsure restart the set and verify no Fault lamps are illuminated. Are they all off? 2) Test the Fault Monitor by putting S1 in...
  14. K

    mep 803a power at lugs one time

    Test the Contactor Closed Lamp to verify it's working. To do so put S1 in Prime/Run and press on the lamp lens to verify it illuminates. With the set running and HOLDING S5 up does the contactor lamp illuminate?
  15. K

    MEP831A won’t turn off only when disconnecting battery

    No problem. I have them in stock ready to ship.
  16. K

    MEP831A won’t turn off only when disconnecting battery

    It's a bad SLC100 Governor Controller.
  17. K

    MEP831A won’t turn off only when disconnecting battery

    I assume the video was normal running and then moving S1 to the STOP position? Still using the factory SLC100 Governor Controller?
  18. K

    Updated - MEP-803a Has arrived! (Formerly "On Its way")

    No tipping issues at all. I roll it outside 2-4 times a month. Never had an issue. Concrete floor onto asphault with about a 1/2" drop. With a design tweek you could locate the casters farther apart if it makes you feel better. The casters were take off's from work. As I recall they were...
  19. K

    Updated - MEP-803a Has arrived! (Formerly "On Its way")

    Lots of great ideas in this thread --> Casters My implementation is post # 3 Simple 2x6 construction and 4 heaver casters. Works great and doesn't waste any precious floor space in my garage. If you go the casters route be sure to use 2 fixed and two swiveling casters and not 4 swiveling casters.