• Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!

  • Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.

Search results

  1. K

    Mep831 help

    Here is a link to download GAC's adjustment procedure. It has a step or two that the -13 TM doesn't include. It covers the tweek that may be needed to the black knob position that CallMeColt mentioned above. Link---> Adjustment Procedure
  2. K

    Mep831 help

    You have a few problems from what I can see in your pictures. The first BIG one is the black knob on the front of the mechanical governor plate is in the STOP position. You need to loosen the knob and move it as far as it will toward the START position and then tighten the knob. The two...
  3. K

    MEP 802A Aux fuel tank option

    For those looking for a mate to the Aux Fuel inlet.. ---> Aux Fuel Fitting
  4. K

    MEP-803 DC Ammeter

    Possibly here ---> Oshkosh
  5. K

    Mep 803a no AC

    You're most welcome!
  6. K

    MEP-802/803/831 Generator Control & Parameter Monitor by WIFI Demo

    Yes requires returning just the controller card to me so I can add your homes WiFi router credentials to it. No charge to do that update other than return shipping.
  7. K

    MEP-802/803/831 Generator Control & Parameter Monitor by WIFI Demo

    A few internet connectivity enhancements have been made to the Remote Start kits that I offer. Here are the current connectivity options... 1) The original version (AKA Version 1) provids a direct WiFI link between your smart phone and the controller - no router or internet required. Great...
  8. K

    MEP 804b wont crank

    It appears your new one is made for an 804A
  9. K

    MEP802a alternator rectifier part numbers?

    All the part numbers can be looked up in TM 9-6115-641-24P The TM can be downloaded from the TM section of the forum.
  10. K

    Corrosive coolant

    No reason you couldn't. Both use the same inlet housing 186-6189
  11. K

    MA MEP-802A, MEP-803A WiFi 2-Wire Remote Start Parameter Monitoring System

    ** New info 1-18-21 If using a Version 2 you can easily make your Controller available on the internet so it's accessible from anywhere. To do so just requires some new settings in your router such as a Static IP address for the Controller and setting up "Port Forwarding" .
  12. K

    Mep-002a fuel pump question

    See section 7-3 of TM 5-6115-584-34 7-3. EXTERNAL GOVERNOR PARTS AND SPEED CONTROL ASSEMBLY.
  13. K

    MEP 803 Voltage Regulator

    Dave, Some gauges have the terminals reversed. All depends on who the gauge vendor that supplied the gauges. Great to hear she's up and running! Kurt
  14. K

    MEP 803 Voltage Regulator

    Dave, Here is an easy way to find the correct terminal. Turn S1 to the PRIME/RUN position. You should hear the fuel pump running. With a meter measure the DC voltage at each of the terminals on M7 with respect to ground. One if them will have ~24 volts DC on it. That's the one the M7-I wire...
  15. K

    Battery issues?

    There are no diodes in the stock battery cables.
  16. K

    MEP-803a "click" no start

    The -24 TM
  17. K

    MEP 803 Voltage Regulator

    David, Check to be sure you have the VR's lead labelled M7-I on the correct terminal on the back of M7. The terminals usually have an "S" and and "I" embossed in the case of the meter. You need to be sure the lead is on the "I" terminal. Having it on the incorrect terminal will cause what you...
  18. K

    Mep-802a ac short fault.

    Now that I'm back to a real computer and reference materials I can give you more info on the K8 "Relay" operation and expand on the voltage tests you can do at the K8 Overload/Short Circuit "Relay". The K8 relay monitors the current load on each of the 3 legs of the generator to determine if the...
  19. K

    Mep-802a ac short fault.

    If there is a section on testing K8 it would be in the -24 TM. The tests I mentioned are my own used to narrow down problems with Overload and Short Circuit Faults.
  20. K

    Mep-802a ac short fault.

    The Battle Short switch cannot inhibit Short Circuit faults. See the -10 TM Poor contact in the S6 and S8 can cause this type of issue. With the set OFF exercise S6 and S8 by moving them repeatedly thru all positions and then set them back to their needed positions before starting. If you...
Top
AdBlock Detected

We get it, advertisements are annoying!

Sure, ad-blocking software does a great job at blocking ads, but it also blocks useful features of our website like our supporting vendors. Their ads help keep Steel Soldiers going. Please consider disabling your ad blockers for the site. Thanks!

I've Disabled AdBlock
No Thanks